2028 and 2030 are closer than you think
With the EU’s revised Energy Performance of Buildings Directive (EPBD), the transition towards zero-emission buildings is accelerating. For HVAC filter manufacturers and OEMs, this puts a familiar technical parameter in a new perspective: pressure drop and its impact on energy consumption.
Choosing the right filter media is no longer just about filtration efficiency. It is also about how the filter performs throughout its service life – and what that means for the energy required to maintain airflow.
EPBD: New requirements for building energy performance
The revised Energy Performance of Buildings Directive (EU) 2024/1275 introduces important milestones:
1 January 2028: New buildings owned by public bodies must be zero-emission buildings.
1 January 2030: All new buildings must be zero-emission buildings.
2030 and 2033: Minimum energy performance standards will address the worst-performing 16% and 26%, respectively, of existing non-residential buildings, subject to national implementation and exemptions.
The EPBD does not prescribe specific filter media or pressure drop limits. However, ventilation energy contributes to a building’s overall energy performance, making efficient HVAC system design increasingly relevant.
For filter manufacturers, this creates an opportunity to help customers reduce operating energy requirements through better-performing filtration solutions.
Why HVAC filter pressure drop matters
Every air filter creates resistance to airflow. The higher the pressure drop, the more energy a fan may need to maintain the required airflow.
And initial pressure drop is only part of the picture.
As a filter collects dust, its resistance typically increases. This means that dust holding capacity and pressure drop development throughout the filter’s operating life are important factors when evaluating energy performance.
According to Eurovent’s air filter energy efficiency methodology, average pressure drop is a key factor when calculating filter-related fan energy consumption.
At constant airflow, reducing average pressure drop can therefore reduce the energy required by the fan.
S-Series: Documented performance beyond initial efficiency
JP Air Tech’s S-Series multilayer filter media are designed to combine efficient particle capture with low airflow resistance and high dust holding capacity.
In a comparison of finished 592 × 592 mm filters, JP Air Tech’s JX101 (ePM1 55%) was tested against a glass-fibre filter (ePM1 50%).
The comparison showed:
-
15% lower initial pressure drop
-
23% lower pressure drop after 200 g of dust had been fed to the filters
-
66% higher dust holding capacity
These results illustrate how filter media selection can influence performance beyond the initial efficiency rating.
The figures relate to the specific tested filter configurations. Performance in other filter designs and operating conditions must be verified separately.
What could a 10 Pa reduction mean in energy savings?
Even a relatively small reduction in average pressure drop can make a measurable difference.
At an airflow of 3,400 m³/h, with 6,000 operating hours annually and 50% fan efficiency, a 10 Pa reduction in average pressure drop corresponds to approximately 113 kWh in filter-related fan energy savings per filter per year.
A separate illustrative calculation based on JP Air Tech’s flat-sheet media test data indicates approximately 15% lower filter-related fan energy in the modelled comparison, equivalent to around 215 kWh saved per filter per year.
At an electricity price of €0.25/kWh, that represents approximately €54 in annual savings per filter.
For an installation using eight filters, the illustrative annual savings increase to approximately 1,723 kWh, corresponding to €431 at the same electricity price.
These figures are estimates based on defined test conditions and assumptions, not guaranteed savings or a Eurovent filter energy rating. Actual results depend on filter configuration, operating conditions, airflow control and fan efficiency.
Act now. Test your filters.
Could your current filter media deliver better energy performance?
At JP Air Tech, we help filter manufacturers and OEMs evaluate alternative media solutions based on their specific filtration efficiency, airflow and dust loading requirements.
Our in-house testing capabilities support performance comparisons and the qualification of alternative filter media.
Let’s put your filters to the test.
Contact our technical sales team to discuss a matched trial at the same ePM1 class and airflow.
Keep the numbers handy
Want the key figures in one place?
We’ve gathered the EPBD deadlines, S-Series test results and illustrative energy savings in a one-page overview – easy to save, share and revisit when evaluating your filter media options.